Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
9.21.3.9.(1) | Application | Intent |
OS2 | OP1 | OH1 | OS3 | OS1 |
Objective | OS2 Structural Safety |
Attribution | |
Application | Application 1: Mortar bed for chimney liners for
rectangular masonry or concrete chimneys that
are not more than 12 m in height, for solid-fuel-burning appliances having a combined total rated heat output
of 120 kW or less, in buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9]. Application 2: This also applies to rectangular masonry
or concrete chimneys, in buildings to which
Part 6 applies [see Sentence 1.3.3.2.(1) of Division A for application
of Part 6], as stated in Sentence 6.3.1.2.(1). |
Top of Page | |
Intent | Intent 1: To limit the probability that flue gas condensate will leak
from joints in chimney liners, which could lead to corrosion or freeze-thaw
damage to surrounding masonry, which could lead to the structural failure
of the chimney, which could lead to harm to persons. |