Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.21.4.7.(1)
OP1OS1
ObjectiveOP1 Fire Protection of the Building
Attribution
Application
Application 1: 
Cleanouts for chimney flues for rectangular masonry or concrete chimneys that are not more than 12 m in height and that serve fireplaces or appliances having a combined total rated heat output of 120 kW or less, in buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Application 2: 
This also applies to rectangular masonry or concrete chimneys, in buildings to which Part 6 applies [see Sentence 1.3.3.2.(1) of Division A for application of Part 6], as stated in Sentence 6.3.1.2.(1).
Top of Page
Intent
Intent 1: 
To limit the probability that smouldering material will accumulate at the bottom of the chimney, which could lead to:
  • an increase in the severity of a chimney fire,
  • the ignition of the cleanout frame or door, or
  • the spillage of smouldering material onto combustible material.
This is to limit the probability of the ignition of combustible building components, which could lead to damage to the building.