Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.23.12.3.(1)
OS2OP2OH1OH4OS1OS3
ObjectiveOS3 Safety in Use
Attribution
[F22-OS3.1] Applies to floors and elements that support floors.
[F22-OS3.7] Applies to walls, and elements that support walls, that contain doors or windows required for emergency egress.
Application
Application 1: 
Maximum spans for wood lintels, in wood-frame constructions to which Section 9.23. applies [see Sentence 9.23.1.1.(1) for application of Section 9.23.]:
  • in buildings of residential occupancy,
  • where wall studs exceed 38 mm by 64 mm in size,
  • where the spans of supported joists do not exceed 4.9 m, and
  • where the spans of trusses do not exceed 9.8 m.
Top of Page
Intent
Intent 1: 
To limit the probability of excessively long spans, which could lead to an inability to resist expected gravity and lateral loads around openings.
This is to limit the probability of:
  • compromised structural integrity,
  • where elements support or are part of an environmental separator, the failure of required environmental separation elements, which could lead to deterioration, or
  • an inability to resist expected loads, which could lead to:
    • the excessive deflection or vibration of floors, or
    • the excessive movement or deformation of walls.
This is to limit the probability of:
  • compromised operation of doors or windows required for egress in an emergency, and
  • persons losing their balance, tripping or falling.
This is to limit the probability of harm to persons.