Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
9.23.13.8.(7) | Application | Intent |
OS2 | OP2 | OH1 | OS1 | OS3 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Fastening together of lumber ceiling joists that are
shorter than the width of the roof and that act as ties for rafters that are
not supported at the ridge, in wood-frame constructions to which Section 9.23. applies
[see Sentence 9.23.1.1.(1) for application of Section 9.23.].
|
Top of Page | |
Intent | Intent 1: To limit the probability of the inadequate splicing of ceiling
joists, which could lead to ceiling joist splices being unable to resist the
tension forces imposed by expected gravity and lateral loads on rafters, which
could lead to the lower end of rafters moving outward, which could lead to:
Where assemblies are required to provide fire
resistance, this is to limit the probability of compromised fire resistance
of the assembly, which could lead to harm to persons.
|