Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.23.15.7.(1)
OS2OP2OH1OH4OS3
ObjectiveOS3 Safety in Use
Attribution
Application
Application 1: 
Minimum thickness of roof sheathing for flat roof surfaces used as walking decks, in wood-frame constructions to which Section 9.23. applies [see Sentence 9.23.1.1.(1) for application of Section 9.23.].
Top of Page
Intent
Intent 1: 
To limit the probability of an inadequate grade or thickness of sheathing relative to framing member spacing and edge support, which could lead to an inability to resist expected gravity and lateral loads, which could lead to excessive deflection, which could lead to damage to roofing or walking surfaces.
For floors and elements supporting floors, this is to limit the probability of persons tripping or falling, which could lead to harm to persons.