Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.24.2.1.(1)
OP2OS2OS3
ObjectiveOS2 Structural Safety
Attribution
Application
Application 1: 
Minimum size and maximum spacing of steel studs in non-loadbearing interior walls of buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Exceptions: 
except as stated in Article 9.24.2.4., which applies to fire separations required to have a fire-resistance rating that have openings for doors.
Top of Page
Intent
Intent 1: 
To limit the probability of an inadequate cross-sectional area, or excessive slenderness or spacing, which could lead to inadequate strength or rigidity.
This is to limit the probability of the excessive movement or deformation of walls, which could lead to the structural failure of walls, which could lead to harm to persons.