Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.24.3.2.(2)
OS1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Attachment of steel studs that allows for their expansion, in non-loadbearing exterior and interior walls required to have a fire-resistance rating, in buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Exceptions: 
except as stated in Article 9.24.3.6., which applies to attachments between studs and bottom runners only, by means of screws, crimping or welding around wall openings and elsewhere where necessary to keep the studs in alignment during construction.
Top of Page
Intent
Intent 1: 
To limit the probability that the connection of studs to top and bottom runners will be rigid, which could hinder the linear expansion of steel studs during a fire, which could lead to the buckling of studs, which could lead to the premature failure of fire-rated assemblies, which could lead to harm to persons.