Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
9.24.3.7.(1) | Application | Intent |
OS1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Doubling of steel studs at openings for fire
dampers in non-loadbearing exterior and
interior walls required to have a fire-resistance rating,
in buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9]. |
Top of Page | |
Intent | Intent 1: To limit the probability that the wall framing around fire
dampers will have insufficient strength to support the dampers, which could
lead to compromised operation of fire dampers in the event of a fire, which
could lead to the breaching of fire-rated assemblies, which could lead to
harm to persons. |