Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.29.5.10.(1)
OS1
ObjectiveOS1 Fire Safety
Attribution
[F81-OS1.2] Applies where the finishing of joints is required to maintain required fire-resistance ratings.
Application
Application 1: 
Minimum temperature for taping and finishing single-layer installations of gypsum board interior wall and ceiling finishes on wood furring or framing, in buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Application 2: 
This also applies to the protection of foamed plastics that form part of a wall or ceiling assembly in combustible construction:
  • in buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], as stated in Clause 9.10.17.10.(1)(a), and
  • in buildings to which Part 3 applies [see Sentence 1.3.3.2.(1) of Division A for application of Part 3] that are permitted to be of combustible construction, as stated in Clause 3.1.4.2.(1)(a).
Top of Page
Intent
Intent 1: 
Where the finishing of joints is required to maintain required fire-resistance ratings, to limit the probability of incomplete drying of gypsum wallboard cement, which could lead to inadequate adhesive characteristics, which could lead to delamination, which could lead to a loss of fire resistance, which could lead to the growth and spread of fire, which could lead to harm to persons.
Top of Page