Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.32.3.13.(5)
OH1
ObjectiveOH1 Indoor Conditions
Attribution
Application
Application 1: 
Minimum vertical distance from the bottom of exhaust outlets to:
  • finished ground, or
  • any nearer and lower permanent horizontal surface.
This applies to self-contained heating-season mechanical ventilation systems serving single dwelling units with 5 or fewer bedrooms that are supplied with electrical power and a heating system, in buildings to which:
  • Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], or
  • Part 6 applies [see Sentence 1.3.3.2.(1) of Division A for application of Part 6 and Sentence 6.2.2.1.(3)].
Exceptions: 
except as stated in Sentence 9.32.3.1.(1), which applies to heating-season mechanical ventilation systems designed to comply with CAN/CSA-F326-M.
Top of Page
Intent
Intent 1: 
To limit the probability of insufficient vertical clearance, which could lead to the blockage of exhaust openings by vegetation, earth or debris, which could lead to inadequate exhaust airflow, which could lead to excessive positive pressure in dwelling units, which could lead to:
  • the inadequate control of airborne pollutants, or
  • condensation within assemblies.
This is to limit the probability of the generation of pollutants from biological growth or from materials that become unstable on wetting, which could lead to negative effects on the air quality of indoor spaces, which could lead to harm to persons.