Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
9.33.6.3.(1) | Application | Intent |
OS1 | OP1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Flame resistance of tape used for sealing duct joints
in air ducts, plenums and other parts of air duct
distribution systems serving heating systems in which the rated heat input
does not exceed 120 kW and serving only one dwelling
unit, in buildings to which Part 9 applies
[see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Application 2: This also applies to ventilation ducts and their fittings,
as stated in Sentence 9.32.3.11.(1). |
Top of Page | |
Intent | Intent 1: To limit the probability of the ignition of combustible
material, which could lead to the spread of fire and smoke throughout the
building, which could lead to harm to persons. |
Top of Page |