Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.33.6.4.(7)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
(a),(b) [F01,F03-OS1.1]
Application
Application 1: 
Interruption of combustible coverings and linings of ducts, including associated adhesives and insulation, at the immediate area of operation of heat sources, in air duct distribution systems serving heating systems in which the rated heat input does not exceed 120 kW and serving only one dwelling unit, in buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Application 2: 
This also applies to ventilation ducts and their fittings, as stated in Sentence 9.32.3.11.(1).
Top of Page
Intent
Intent 1: 
To limit the probability of:
  • combustible coverings and linings of ducts, adhesives and insulation being exposed to elevated temperatures, which could lead to fire, or
  • combustible material that has ignited contributing to the spread of fire from one fire compartment to another.
This is to limit the probability of harm to persons.