Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
9.33.6.7.(5) | Application | Intent |
OS1 | OP1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Minimum clearance for combustible ducts
in concrete slabs-on-ground that are connected to a furnace supply plenum in which the rated heat input does not exceed 120
kW and serving only one dwelling unit,
in buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9]. Application 2: This also applies to ventilation ducts and their fittings,
as stated in Sentence 9.32.3.11.(1). |
Top of Page | |
Intent | Intent 1: To limit the probability of exposure to hot air in the vicinity
of furnace heat exchangers, to heat radiated from furnace heat exchangers,
or to embers or flames from objects dropped into registers, which could lead
to the ignition of combustible duct material, which could lead to harm to
persons. |