Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
9.33.6.14.(3) | Application | Intent |
OS1 | OP1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Noncombustibility of return
ducts, in air duct distribution systems serving solid-fuel-burning furnaces in which the rated heat input does not exceed 120
kW and serving only one dwelling unit,
in buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9]. |
Top of Page | |
Intent | Intent 1: To limit the probability of the ignition of return ducts
by heat (transferred from excessively hot air) that has entered the return
ducts upon failure of a circulating fan or other bonnet-temperature-limiting
device, which could lead to harm to persons. |