Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.10.12.4.(2)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Portion of any soffit or other surface enclosing a projection that is:
  • less than 2.5 m vertically above a window or door, and
  • less than 1.2 m from either side of the window or door.
This applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], where:
Exceptions: 
except as stated in:
  • Sentence 9.10.12.4.(4), which applies when the soffit or other surface is completely separated from the remainder of the attic or roof space by fire stopping, and
  • Sentence 9.10.12.4.(5), which applies where all suites spanned by a common attic or roof space or situated above or below the projecting floor are sprinklered.
Top of Page
Intent
Intent 1: 
To limit the probability that fire will spread from a suite through openings [e.g. windows or doors] in the exterior wall and then through openings in soffits, which could lead to the spread of fire through the common attic or roof space or the floor above to other suites, which could lead to harm to persons.