Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.10.12.4.(4)
+
Application
Application 1: 
Soffits or other surfaces that enclose projections as described in Sentence 9.10.12.4.(1), where the soffits or other surfaces are completely separated from the remainder of the attic or roof space by fire stopping.
This applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], where:
  • a common attic or roof space spans more than 2 suites of residential occupancy and projects beyond the exterior wall of the building, and
  • the projection is
    • less than 2.5 m vertically above a window or door, and
    • less than 1.2 m from either side of the window or door.
Top of Page
Intent
Intent 1: 
To exempt portions of soffits or other surfaces that enclose a projection from the requirements of Sentence 9.10.12.4.(2), if certain measures are taken [i.e. the soffits or other surfaces are completely separated from the remainder of the attic or roof space by fire stopping], on the basis that the spread of fire to the attic or roof space is controlled by the fire stopping.