Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.10.13.13.(1)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Installation of fire dampers in ducts that penetrate assemblies required to be fire separations with a fire-resistance rating.
This applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Exceptions: 
except as exempted in:
  • Sentence 9.10.5.1.(4), which applies to openings that lead to ducts within a membrane ceiling that forms part of an assembly assigned a fire-resistance rating,
  • Sentence 9.10.13.13.(2), which applies to noncombustible branch ducts that pierce a required fire separation where the duct
    • has a melting point not below 760°C
    • has a cross-sectional area less than 130 cm2, and
    • supplies only air-conditioning units or combined air-conditioning and heating units discharging air at not more than 1.2 m above the floor,
  • Sentence 9.10.13.13.(3), which applies to noncombustible branch ducts that pierce a required fire separation around an exhaust duct riser in which the air flow is upward,
  • Sentence 9.10.13.13.(4), which applies to noncombustible ducts that penetrate a fire separation separating a vertical service space from the remainder of the building, and
  • Sentence 9.10.13.13.(5), which applies to ducts serving commercial cooking equipment.
Top of Page
Intent
Intent 1: 
To limit the probability that fire will spread from one fire compartment to another fire compartment through openings in a fire separation, which could lead to harm to persons in the other fire compartment.
Intent 2: 
To expand the application of Articles 3.1.8.4. and 3.1.8.9. to Part 9 buildings.