Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
9.10.14.4.(6) | Application | Intent |
+ |
Application | Application 1: Maximum aggregate area of unprotected
openings in an exposing building face of
a storey, in buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9], where:
Exceptions:
except as stated in Sentence 9.10.15.1.(1), which applies to buildings that contain only dwelling
units and have no dwelling unit above
another dwelling unit.
|
Top of Page | |
Intent | Intent 1: To exempt certain exposing building faces from the requirements
of Sentence 9.10.14.4.(1), which would otherwise limit the area of unprotected
openings, and permit unlimited unprotected openings, on the basis that the
building face is readily accessible to firefighters [who will be able to effectively
carry out fire suppression operations] and the limiting distance is not less
than 9 m. |