Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.17.2.2.(1)
OS2OP2OH1OH4OS3
ObjectiveOS2 Structural Safety
Attribution
[F22-OS2.3] Applies to elements that support or are part of an environmental separator.
Application
Application 1: 
Fastening of columns, in buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], that are used to support:
  • beams carrying loads from not more than 2 wood-frame floors where
    • the supported length of joists bearing on such beams does not exceed 5 m, and
    • the live load on any floor does not exceed 2.4 kPa,
  • beams or header joists carrying loads from not more than 2 levels of wood-frame balconies, decks or other accessible exterior platforms, or 1 level plus roof, where:
    • the supported length of joists bearing on such beams or rim joists does not exceed 5 m,
    • the sum of the specified snow and occupancy loads on the platform-type construction or roof does not exceed 4.8 kPa,
    • the platform serves only a single suite of residential occupancy, and
    • the platform does not serve as a required exit, and
  • carport roofs.
Top of Page
Intent
Intent 1: 
To limit the probability of inadequate fastening, which could lead to columns becoming accidentally dislodged.
This is to limit the probability of compromised structural integrity, which could lead to:
  • structural failure,
  • uplift or sliding, or
  • for environmental separators or elements supporting an environmental separator, excessive deformation or deflection of exterior walls or roofs, which could lead to the displacement or failure of required environmental separation elements, which could lead to the deterioration of building elements.
This is to limit the probability of harm to persons.
Top of Page