Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.21.4.5.(1)
+
Application
Application 1: 
Bracing for rectangular masonry or concrete chimneys that are not more than 12 m in height and serve fireplaces or appliances having a combined total rated heat output of 120 kW or less, in buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9].
Exceptions: 
except as stated in Sentence 9.21.4.5.(2), which applies to chimneys:
  • with no horizontal outside dimension less than 400 mm, and
  • that extend not more than 3.6 m above the roof or the masonry wall of which they form a part.
Application 2: 
This also applies to bracing for rectangular masonry or concrete chimneys that are not more than 12 m in height and serve fireplaces or appliances having a combined total rated heat output of 120 kW or less, in buildings to which Part 6 applies [see Sentence 1.3.3.2.(1) of Division A for application of Part 6], as stated in Sentence 6.3.1.2.(1).
Top of Page
Intent
Intent 1: 
To expand the application of Subsection 4.3.2., which provides design criteria for plain and reinforced masonry, to include chimneys to which Part 9 applies.