Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

9.25.1.2.(5)
+
Application
Application 1: 
Position of sheet and panel-type materials relative to the thermal insulation, in buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], where:
  • the materials:
    • have an air leakage characteristic less than 0.1 L/(s•m2) at 75 Pa,
    • have a water vapour permeance less than 60 ng/(Pa•s•m2), and
    • are installed in a building assembly that is required to be insulated (see Article 9.25.2.1.),
  • the mild climate indicator determined in accordance with Sentence 9.25.1.2.(6) is less than or equal to 6 300, and
  • the intended use of the interior space:
    • requires the indoor relative humidity to be maintained above 60% over the heating season, and the ventilating and air-conditioning system is designed to maintain that relative humidity, or
    • will result in an average monthly indoor relative humidity above 60% over the heating season, and the ventilating and air-conditioning system does not have the capacity to reduce the average monthly relative humidity to 60% over that period.
Exceptions: 
except as stated in Sentence 9.25.1.2.(3), which applies to wood-based sheathing materials that conform to Sentence 9.23.16.2.(1) and are not more than 12.5 mm thick.
Top of Page
Intent
Intent 1: 
To limit the application of Clause 9.25.1.2.(2)(b) and to expand the application of Part 5 to building assemblies that:
  • incorporate low permeance materials other than as cladding or on the warm side of the assembly, and
  • are more susceptible to condensation due to high interior relative humidity over the heating season in milder climates.