Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.7.5.(6) | Application | Intent |
OP1 | OS1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Minimum fire-resistance rating of fire separations that separate solid and liquid Class
5 oxidizing substances from the remainder of the building.
This applies to buildings or parts of buildings used for the short- or long-term storage of dangerous goods in packages or containers when stored
in single fire compartments in quantities greater
than those shown in Table 3.2.7.1., whether raw or waste materials,
goods in process, or finished goods.
|
Top of Page | |
Intent | Intent 1: To limit the probability that a fire in the oxidizer storage
area will spread to other parts of the building, which could lead to harm
to persons. |