Warning This information has been archived because it is outdated and no longer relevant.

Archived Content

Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

4.2.7.5.(2)
OS1OP1+
Attribution
(b)
Application
Application 1: 
Size [quantity] and clearances of individual storage areas [in Table 4.2.7.5.B..] of indoor protected rack storage of flammable liquids, combustible liquids or unstable liquids, where such liquids are:
  • in storage areas as specified in Clause 4.2.7.2.(1)(a),
  • in bulk plants as stated in Sentence 4.7.2.4.(1),
  • in mercantile occupancies in quantities in excess of those permitted in Sentences 4.2.5.1.(2) to (4)[as stated in Sentence 4.2.5.1.(5)],
  • in closed containers conforming to Clauses 4.2.3.1.(1)(a) to (d) that have a capacity of not more than 230 L, or closed portable tanks conforming to Clause 4.2.3.1.(1)(e) that have an individual capacity of not more than 2 500 L, and
  • in buildings separated from adjacent buildings by a firewall having a fire-resistance rating of at least 4 h, or by spatial separation in conformance with the National Building Code of Canada.
Exceptions: 
except as exempted in:
  • Article 4.1.5.8., which applies to the storage of Class I liquids in basements,
  • Sentence 4.1.1.1.(3), which applies--in part--to oil burning equipment and the storage of aerosol products, and
  • Sentence 4.2.1.1.(2), which applies--in part--to:
Top of Page
Intent
Intent 1: 
To clarify what quantity limits apply to a storage situation for which there would otherwise be no applicable requirement in Tables 4.2.7.5.A. and 4.2.7.5.B.., referenced in Sentences 4.2.5.1.(2) and 4.2.7.5.(1).
Intent 2: 
To state the allowable quantities per individual storage area for protected rack storage.
Top of Page