Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

4.3.5.3.(2)
OS1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Manifolding of normal vent piping for aboveground storage tanks containing Class I liquids with vent piping for such tanks containing Class II or IIIA liquids, in buildings, structures and open areas.
Exceptions: 
except:
  • as exempted in Sentences 4.1.1.1.(2) and (3), which apply to unique hazards at process plants, in transportation, for oil burning equipment, on farms and isolated construction projects, and the storage of aerosol products, and
  • as provided in Sentence 4.10.5.1.(1), which applies to distilled beverage alcohol at distilleries.
Top of Page
Intent
Intent 1: 
To limit the probability of the contamination of Class II or IIIA liquid vapours with Class I liquid vapours, which could lead to the accumulation and subsequent ignition of vapour, which could lead to harm to persons.
Top of Page