This information has been archived because it is outdated and no longer relevant.
Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
4.7.4.1.(2) | Application | Intent |
| OP1 | OS1 | OP3 | OH5 |
| Objective | OH5 Hazardous Substances Containment |
| Attribution | |
| Application | Application 1: Minimum distance from a loading structure to a railway
line at bulk plant rail loading and unloading facilities, including at buildings for the shelter of personnel or pumps as stated
in Sentence 4.7.4.1.(3). This applies to properties
or portions of properties where flammable liquids or combustible liquids are received in bulk quantities
and are stored or handled for the purpose of being distributed.
Exceptions:
except as exempted in Sentences 4.1.1.1.(2) and (3), which apply to unique hazards
at process plants, in transportation, for oil
burning equipment, on farms and isolated construction projects, and the storage
of aerosol products.
|
| Top of Page | |
| Intent | Intent 1: To limit the probability that normal train operations will
lead to excessive vibrations or ground settling, which could lead to the failure
of flammable or combustible liquid piping systems at the loading and unloading
facilities, which could lead to the escape of liquid, which could lead to
harm to the public. Intent 2: To limit the probability that a train derailment will lead
to impact with or damage to the flammable or combustible liquid piping systems
at the loading and unloading facilities, which could lead to the failure of
the piping systems, which could lead to the escape of liquid, which could
lead to harm to the public. |
| Top of Page |