Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

4.1.7.6.(1)
OS1OS1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Recirculation of exhaust air from mechanical ventilation systems required in Article 4.1.7.2., and where:
  • the flammable vapour concentration in the exhaust air is continuously monitored,
  • interlocks are provided so that if such concentration exceed 25% of the lower explosive limit, an alarm is sounded, recirculation is stopped and exhaust air is directed outside the building, and
  • Class I liquids are stored.
Exceptions: 
except where such storage consists only of closed containers and no dispensing operations are performed, or Class I or II liquids are processed, dispensed or used.
Exceptions: 
except:
  • as exempted in Sentences 4.1.1.1.(2) and (3), which apply to unique hazards in process plants, transportation, oil burning equipment, farms, isolated construction projects, and aerosol products, and
  • when in conformance with the appropriate provincial or territorial legislation.
Application 2: 
This also applies, as required in Clause 3.2.8.2.(1)(e), to dedicated storage rooms for cylinders of Class 2.1 flammable gases.
Exceptions: 
except:
  • where the quantities in a single fire compartment do not exceed 25 kg in the case of heavier-than-air gases,
  • where the quantities in a single fire compartment do not exceed those permitted in Sentence 3.2.8.2.(2) in the case of lighter-than-air gases,
  • as exempted in Sentence 3.1.1.4.(1), which applies to Class 2 gas manufacturing and dispensing facilities, and
  • for aerosols covered in Subsection 3.2.5.
Top of Page
Intent
Intent 1: 
To remove the obligation, in Sentences 4.1.7.4.(1) and 5.4.5.2.(1), for exhaust air to be discharged outside the building and to permit its recirculation inside the building if a fail-safe system is provided. This is to limit the probability that vapour will accumulate, which could lead to the ignition of vapour from a nearby ignition source, which could lead to harm to persons.