Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

4.6.6.5.(5)
OS1OP1OH5
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Provision and location of automatically operated valves designed to open only when the dispenser is being operated and to prevent gravity draining of the tank in the event of a rupture of the supply line to the dispenser, at marine fuel-dispensing stations, where:
  • such valves are used in systems for dispensing flammable liquids or combustible liquids,
  • such liquids are transferred from bulk storage to individual or multiple dispensers by pumps located elsewhere than at the dispensers, and
  • storage tanks are elevated above the dispenser.
Exceptions: 
except as exempted in Sentences 4.1.1.1.(2) and (3), which apply to specific hazards at process plants, in transportation, for oil-burning equipment, on farms and isolated construction projects, and the storage of aerosol products.
Top of Page
Intent
Intent 1: 
To limit the probability that damage or rupture of the supply line to the dispenser will lead to gravity draining of the tank, which could lead to the escape and spread of liquid, which could lead to the ignition of vapour from a nearby ignition source, which could lead to harm to persons.