This information has been archived because it is outdated and no longer relevant.
Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
4.6.6.5.(5) | Application | Intent |
OS1 | OP1 | OH5 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Provision and location of automatically operated valves
designed to open only when the dispenser is being operated and to prevent
gravity draining of the tank in the event of a rupture of the supply line
to the dispenser, at marine fuel-dispensing stations,
where:
Exceptions:
except as exempted in Sentences 4.1.1.1.(2) and (3), which apply to specific hazards
at process plants, in transportation, for oil-burning
equipment, on farms and isolated construction projects, and the storage of
aerosol products.
|
Top of Page | |
Intent | Intent 1: To limit the probability that damage or rupture of the supply
line to the dispenser will lead to gravity draining of the tank, which could
lead to the escape and spread of liquid, which could lead to the ignition
of vapour from a nearby ignition source, which could lead to harm to persons.
|
Top of Page |