Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

5.6.1.13.(2)
OS1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Identification and subsequent removal of tanks, piping and machinery reservoirs containing combustible liquids or flammable liquids, or that are likely to contain flammable vapours, and that have been drained and purged, in buildings or parts of buildings undergoing demolition, including any incomplete or abandoned buildings, where removal of the equipment prior to demolition is impracticable.
Exceptions: 
except as stated in Sentence 5.6.1.1.(2), which applies to construction or demolition activities involving buildings that:
  • do not pose an exposure hazard to other buildings, or
  • pose a minimal fire hazard to occupants.
Top of Page
Intent
Intent 1: 
To supersede the requirement in Sentence 5.6.1.13.(1), where it is impracticable to remove drained and purged equipment prior to demolition, but only if measures are taken to:
  • limit the probability of damage to the equipment during demolition operations [identification], and
  • eliminate the vapour ignition hazard as soon as possible [removal].