3.1.10.5.(1)

Objective

OP1 Fire Protection of the Building

Attribution

[F03-OP1.2]Applies to portion of Code text: “… the aggregate width of openings shall be not more than 25% of the entire length of the firewall.”

Intent

Intent 1:

To limit the probability of a large number of openings in a firewall, which could lead to the failure of the protective closures for these openings during a fire, which could lead to the spread of fire from an adjacent building to the building, which could lead to damage to the building.

Intent 2:

To limit the probability of a large number of openings in a firewall, which could lead to the failure of the integrity of the firewall, which could lead to the spread of fire from an adjacent building to the building, which could lead to damage to the building.