To supersede the application of Sentence 3.1.8.1.(2), which permits openings in fire separations, even if protected by closures, and not permit any openings in fire separations between a care, treatment or detention occupancy and a repair garage.
This is to limit the probability that smoke from a fire in the repair garage will migrate from the garage into the care, treatment or detention occupancy, which could lead to harm to persons.