3.4.1.6.(2)

Objective

OS3 Safety in Use

Attribution

Intent

Intent 1:

To supersede the requirements of Sentence 3.4.1.6.(1) and permit an increase in the ratio of horizontal exits to all exits, on the basis that:

  • using normal exit facilities in a hospital or nursing home with treatment is difficult,
  • such buildings are fully sprinklered, and
  • there are full-time supervisory staff to assist in evacuation.

This is to limit the probability that persons will not have a choice of sufficient alternative exterior exit routes in the event that routes to horizontal exits are blocked or obstructed in an emergency situation, which could lead to delays in the evacuation or movement of persons to a safe place, which could lead to harm to persons.