9.13.2.5.(1)

Objective

OH1 Indoor Conditions

Attribution

[F40-OH1.1]Applies to dampproofing installed to control the ingress of soil gas.
[F61-OH1.1,OH1.2,OH1.3]Applies to dampproofing installed to control the ingress of moisture.

Intent

Intent 1:

To limit the probability of the ingress of moisture from the ground, not under hydrostatic pressure.

This is to limit the probability of:

  • compromised thermal performance of components intended to provide resistance to heat transfer, which could lead to an inadequate control of the temperature of interior spaces,
  • water accumulation or an inadequate control of relative humidity,
  • the generation of pollutants from biological growth or from materials that become unstable on wetting, or
  • deterioration, which could lead to compromised integrity of the walls.

This is to limit the probability of:

  • negative effects on the air quality of indoor spaces,
  • the inadequate thermal comfort of persons, and
  • contact with moisture.

This is to limit the probability of harm to persons

Intent 2:

Where dampproofing materials are installed to control the infiltration of soil gas, to limit the probability of the infiltration of soil gas, which could lead to negative effects on the air quality of indoor spaces, which could lead to harm to persons.