Sentence 3.2.2.2.(6)

  1. OP1
  2. OS1

Objective

OS1 Fire Safety

Attribution

Intent

Intent 1:

To permit the minimum 6 m aisle width required in Clause 3.2.2.2.(5)(b) to be reduced to 2.4 m if certain conditions are met [the products are stored in racks and the building is sprinklered].

This is to limit the probability that:

  • piles of stored products will collapse prematurely during firefighting operations, which could lead to the obstruction of aisles, which could lead to delays in the egress of emergency responders, which could lead to harm to emergency responders, and
  • a fire will not be suppressed or controlled, which could lead to the spread of fire in the stored products to other parts of the building, which could lead to harm to persons.
Top of Page