Sentence 3.3.3.2.(3)

  1. OP3
  2. OS1

Objective

OP3 Protection of Adjacent Buildings or Facilities from Fire

Attribution

Intent

Intent 1:

To waive the clearance requirements in Sentence 3.3.3.2.(2) if the storage presents a low fire hazard because of the following:

  • the type and arrangement of stored products do not present a high fire hazard [high fire load],
  • a barrier is provided to limit the probability that fire will spread from the stored products to the building, and
  • a sufficient clear space is provided to limit the probability that fire will spread from the stored products to the building where portions of the fire barrier in Clause 3.3.3.2.(3)(b) do not provide the required level of protection.

This is to limit the probability that a fire in the stored products will spread to a building on the same property, which could lead to damage to adjacent buildings or facilities.