Sentence 4.6.5.2.(3)

  1. OH5
  2. OP1
  3. OS1

Objective

OH5 Hazardous Substances Containment

Attribution

Intent

Intent 1:

To exempt marine fuel dispensing stations from the application of Clause 4.6.5.2.(2)(b), which would otherwise require automatic hose nozzle valves, if certain conditions are met [dispensing operations must be continuously attended and hose nozzle valves are manually operated], on the basis that marine fuel dispensing stations pose a higher risk of which could lead to harm to the public [water contamination].

The conditions [that are to be met] are to limit the probability that inadequate control of dispensing operations will lead to an unwanted escape of liquid, which could lead to harm to the public.

Intent 2:

To state the application of Clause 4.6.5.2.(2)(a).

Top of Page