Sentence 3.2.8.2.(1)

  1. +
  2. OS1
  3. +
  4. OS1
  5. OS1
  6. OS1
  7. +
  8. OP1

Objective

OS1 Fire Safety

Attribution

Intent

Intent 1:

To limit the probability that other uses of the storage room will introduce ignition sources near the gas cylinders or add to the combustible loading in the room, which could lead to a fire or explosion, which could lead to harm to persons.

Intent 2:

To supersede the separation requirements stated in Sentences 3.2.7.6.(1) and 3.2.7.17.(1) and prohibit the storage of dangerous goods classified as flammable gases with gases other than compatible dangerous goods classified as compressed gases in the same room.

Top of Page