Sentence 4.10.8.1.(3)

  1. OS1
  2. OP1

Objective

OP1 Fire Protection of the Building or Facility

Attribution

Intent

Intent 1:

To supersede the requirements of Sentence 4.10.8.1.(1), if certain measures are taken [hose stations installed at each exit and spaced so that the travel distance to each station is not greater than 25 m].

This is to limit the probability that fire suppression operations using portable extinguishers will be delayed or ineffective in controlling or suppressing a fire, which could lead to the spread of the fire, which could lead to damage to the building or facility.