Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.1.10.2.(1) | Application | Intent |
OS1 | OP1 | + | OP3 |
Objective | OP1 Fire Protection of the Building |
Attribution |
[F03-OP1.2]
Applies to portion of Code text: “A firewall that separates a building or buildings with floor areas containing a Group E or a Group F,
Division 1 or 2 major occupancy shall
be constructed as a fire separation of noncombustible construction having a fire-resistance rating not less than 4 h …”
|
Application | Application 1: Minimum fire-resistance
rating of a firewall that separates
a building or buildings with floor areas containing Group E or
Group F, Division 1 or 2 major occupancies.
|
Top of Page | |
Intent | Intent 1: To limit the probability that a firewall will have
insufficient fire-resistance, which could lead to the spread of fire
from an adjacent building to the building, which could lead to damage
to the building. Intent 2: To limit the probability that fire will spread from
an adjacent building to the subject building during the time needed
for emergency responders to carry out their duties, which could lead
to damage to the building. |