Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.1.10.3.(1)
OS1OP1+OP3
ObjectiveOS1 Fire Safety
Attribution
[F03-OS1.2] Applies to portion of Code text: “A firewall shall extend from the ground continuously through, or adjacent to, all storeys of a building or buildings so separated …”
Application
Application 1: 
Extension of a firewall from the ground continuously through, or adjacent to, all storeys of a building or buildings so separated.
Exceptions: 
except:
  • for a firewall located above a basement storage garage conforming to Article 3.2.1.2. and commencing at the floor assembly immediately above the storage garage, and
  • as provided in Sentence 3.1.10.1.(3), which allows a firewall to be supported on a structural frame.
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A, and to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9] as stated in Sentence 9.10.11.3.(1).
Top of Page
Intent
Intent 1: 
To limit the probability of a firewall not being continuous, which could lead to gaps or openings in the firewall during a fire, which could lead to the spread of fire from one building to another, which could lead to harm to persons in the building not originally involved in the fire.