Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.1.4.(2) | Application | Intent |
OS1 | OP1 |
Objective | OP1 Fire Protection of the Building |
Attribution | |
Application | Application 1: Minimum fire-resistance rating of loadbearing walls, columns and arches supporting floor
assemblies immediately above basements, in buildings described in Sentence 1.3.3.2.(1) of Division A.
Application 2: This also applies to a crawl space required to be
considered as a basement, as stated in Sentence 3.2.2.9.(1).
Exceptions:
except as exempted in Sentences 3.2.2.42.(3), 3.2.2.43.(3), 3.2.2.44.(3), 3.2.2.45.(3), 3.2.2.46.(3), 3.2.2.47.(3) and 3.2.2.48.(3),
which apply to loadbearing walls, columns and
arches supporting floor assemblies entirely contained within dwelling
units in a building of residential
occupancy.
|
Top of Page | |
Intent | Intent 1: To limit the probability that the supports for a floor assembly
will prematurely fail in a fire situation, which could lead to the collapse
of the floor assembly, which could lead to the spread of fire from the basement
to an upper storey, which could lead to damage to the building.
Intent 2: To limit the probability that the supports for a floor assembly
will prematurely fail in a fire situation, which could lead to the collapse
of the floor assembly, which could lead to damage to the building.
|
Top of Page |