Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.2.28.(2) | Application | Intent |
OP1 | OS1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Building area limits
of Sentence (1) [with a storey in
which more than 10% of the area is classified as a Group A, Division 2 major occupancy] in a building without
a basement that is provided with a fire
separation with a fire-resistance rating not
less than 1 h used to separate the building into fire compartments, each one of which does not exceed
the limits of Clause (b). This applies in buildings whose building height is
restricted to 1 storey and whose building area is restricted to: This applies to buildings to
which Part 3 applies [see Sentence 1.3.3.2.(1) of Division A for application
of Part 3].
Exceptions:
except:
|
Top of Page | |
Intent | Intent 1: To exclude a building from the building area limits of Sentence 3.2.2.28.(1) on the basis that the total area does not exceed twice
the values of Sentence 3.2.2.28.(1) and that the individual areas are
subdivided by a fire separation with a 1 h fire-resistance rating
into areas that individually comply with Sentence 3.2.2.28.(1).
Intent 2: These conditions [fire separation] are to limit the probability
that fire will spread within the storey during the time required to achieve
occupant safety and for emergency responders to perform their duties, which
could lead to harm to persons. |