Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.2.3.11.(1)
OP3OP3
ObjectiveOP3 Protection of Adjacent Buildings from Fire
Attribution
(b) [F03-OP3.1]
Application
Application 1: 
Fire-resistance rating of an exposing building face of noncombustible construction of a building of low hazard industrial occupancy conforming to Article 3.2.2.82., where the limiting distance is not less than 3 m.
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A.
Top of Page
Intent
Intent 1: 
To exempt certain exposing building faces from the requirements of Sentences 3.2.3.1.(1) and 3.2.3.7.(1), (2) and (3), which would otherwise require a fire-resistance rating, on the basis that the building has a low fire load, the exposing building face is of noncombustible construction and the limiting distance is not less than 3 m. These conditions are to limit the probability of the spread of fire from the building to an adjacent building, which could lead to damage to adjacent buildings.