Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.2.5.10.(1)
OS1OP1
ObjectiveOP1 Fire Protection of the Building
Attribution
Application
Application 1: 
Location of standpipe hose connections in exits.
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A in which standpipe systems are installed.
Application 2: 
This also applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], as stated in Sentence 9.10.1.2.(8).
Top of Page
Intent
Intent 1: 
To limit the probability that fire will spread from one storey to another through doors propped open in the exit stair shaft by fire hoses, which could lead to damage to the building.
Intent 2: 
To limit the probability that fire will spread from one storey to the exit stair shaft through doors propped open in the exit stair shaft by fire hoses, which could lead to emergency response operations being delayed or ineffective, which could lead to the spread of fire, which could lead to damage to the building.
Intent 3: 
To supersede the requirements of the standard referenced in Sentence 3.2.5.9.(1) and require a different location for hose connections.