Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.2.5.10.(1) | Application | Intent |
OS1 | OP1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Location of standpipe hose connections in exits.
This applies to buildings described
in Sentence 1.3.3.2.(1) of Division A in which standpipe systems are
installed.
Application 2: This also applies to buildings to
which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application
of Part 9], as stated in Sentence 9.10.1.2.(8). |
Top of Page | |
Intent | Intent 1: To limit the probability that fire will spread from one
storey to another through doors propped open in the exit stair shaft by fire
hoses, which could lead to harm to persons. Intent 2: To limit the probability that fire will spread from one
storey to the exit stair shaft through doors propped open in the exit stair
shaft by fire hoses, which could lead to:
Intent 3: To supersede the requirements of the standard referenced
in Sentence 3.2.5.9.(1) and require a different location for hose connections.
|