Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.
3.3.3.2.(1) | Application | Intent |
OS3 | OS1 |
Objective | OS1 Fire Safety |
Attribution | |
Application | Application 1: Openings in fire separations required
by Sentence 3.3.5.5.(1) between a care or detention
occupancy and a repair garage.
This applies to buildings described
in Sentence 1.3.3.2.(1) of Division A.
Application 2: This also applies to tents and air-supported
structures, as stated in Sentences 3.1.6.1.(1) and 9.10.1.2.(1).
Exceptions:
except as stated in:
|
Top of Page | |
Intent | Intent 1: To supersede the application of Sentence 3.1.8.1.(2) which
permits openings in fire separations, even if protected by closures, and not
permit any openings in fire separations between a care or detention occupancy
and a repair garage. This is to limit the probability
that smoke from a fire in the repair garage will migrate from the garage into
the care or detention occupancy, which could lead to harm to persons.
|
Top of Page |