Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.3.3.2.(1)
OS3OS1
ObjectiveOS3 Safety in Use
Attribution
Application
Application 1: 
Openings in fire separations required by Sentence 3.3.5.5.(1) between a care or detention occupancy and a repair garage.
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A.
Application 2: 
This also applies to tents and air-supported structures, as stated in Sentences 3.1.6.1.(1) and 9.10.1.2.(1).
Exceptions: 
except as stated in:
Top of Page
Intent
Intent 1: 
To supersede the application of Sentence 3.1.8.1.(2) which permits openings in fire separations, even if protected by closures, and not permit any openings in fire separations between a care or detention occupancy and a repair garage.
This is to limit the probability that carbon monoxide, exhaust fumes or other toxic vapours will migrate from the repair garage into the care or detention occupancy, which could lead to the accumulation of such vapours to levels that could pose a risk to human health from short-term exposure, which could lead to harm to persons.