Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.3.3.5.(2)
OS1OP1
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Minimum number and maximum area of fire compartments dividing floor areas containing patients' sleeping rooms in a hospital or nursing home.
Exceptions: 
except as stated in Sentence 3.3.3.5.(3), which applies to floor areas on either side of a horizontal exit.
This applies to care or detention occupancy in buildings described in Sentence 1.3.3.2.(1) of Division A.
Application 2: 
This also applies to tents and air-supported structures, as stated in Sentences 3.1.6.1.(1) and 9.10.1.2.(1).
Exceptions: 
except as stated in:
Top of Page
Intent
Intent 1: 
To limit the probability that patients and emergency responders will be exposed to hazardous conditions during a fire emergency while arrangements are being made to move patients to a safer location, which could lead to harm to persons, including emergency responders.
Intent 2: 
To limit the probability that emergency responders will be exposed to hazardous conditions during a fire emergency while arrangements are being made to move patients to a safer location, which could lead to fire emergency response operations being delayed or ineffective, which could lead to:
  • delays in the evacuation or movement of persons to a safe place, which could lead to harm to persons, including emergency responders, and
  • the spread of fire to other parts of the building, which could lead to harm to persons.