Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.4.2.5.(2)
++
Application
Application 1: 
Location of exits along the perimeter of the floor area and maximum travel distance to at least one exit, where:
  • exits are placed not more than 60 m apart, measured along the perimeter, and
  • each main aisle in the floor area leads directly to an exit.
This applies to floor areas that are intended for occupancy, including mezzanines as stated in Sentence 3.4.2.2.(1), in buildings described in Sentence 1.3.3.2.(1) of Division A.
Application 2: 
This also applies to tents and air-supported structures, as stated in Sentences 3.1.6.1.(1) and 9.10.1.2.(1).
Exceptions: 
except:
Top of Page
Intent
Intent 1: 
To exempt exits located around the perimeter of floor areas from the travel distance limits of Sentence 3.4.2.5.(1), on the basis that the exit spacing is limited and each main aisle leads directly to an exit.
This is allowed on the basis that:
  • occupants will be able to leave before the space becomes untenable in a fire, and
  • emergency responders will be able to enter the building at the exit location and proceed expeditiously by means of the main aisles to problem areas in the building.