Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.6.1.4.(1)
OS1OP1OP3
ObjectiveOP1 Fire Protection of the Building
Attribution
(b) [F03-OP1.2]
Application
Application 1: 
Minimum distance between a fuel-fired appliance and an adjacent wall of a building, where:
  • the fuel-fired appliance is installed on the roof of the building or in another location outside the building, and
  • the wall of the building contains any opening within 3 storeys above and 5 m horizontally from the appliance, except when every opening within these limits is protected by:
    • a closure having a fire-protection rating of not less than 45 min determined in accordance with Article 3.1.8.4., or
    • a wired glass assembly permitted for use in a vertical fire separation and described in Appendix D.
This applies to buildings described in Sentence 1.3.3.2.(1) of Division A.
Application 2: 
This also applies to buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) of Division A for application of Part 9], as stated in Sentence 9.10.1.2.(9).
Top of Page
Intent
Intent 1: 
To limit the probability that a fire involving fuel-fired appliances outside a building will spread into the building through unprotected wall openings, which could lead to damage to the building.