Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats on the "Contact Us" page.

3.6.1.4.(1)
OS1OP1OP3
ObjectiveOS1 Fire Safety
Attribution
Application
Application 1: 
Minimum distance between fuel-fired appliances and:
  • property lines, and
  • adjacent walls of a building, where the wall of the building contains any opening within 3 storeys above and 5 m horizontally from the appliance, except when every opening within these limits is protected by:
    • a closure having a fire-protection rating of not less than 45 min determined in accordance with Article 3.1.8.4., or
    • a wired glass assembly permitted for use in a vertical fire separation and described in Appendix D.
This applies to fuel-fired appliances installed on the roof of a building or in another location outside the building, for buildings described in Sentence 1.3.3.2.(1).
Application 2: 
This also applies to fuel-fired appliances on the roof of buildings to which Part 9 applies [see Sentence 1.3.3.3.(1) for application of Part 9], as stated in Sentence 9.10.1.2.(9).
Top of Page
Intent
Intent 1: 
To limit the probability that a fire involving fuel-fired appliances outside a building will spread into the building through unprotected wall openings, which could lead to harm to persons inside the building.
Intent 2: 
To limit the probability that a fire involving fuel-fired appliances outside a building will spread to an adjacent building, which could lead to harm to persons in the adjacent building.
Intent 3: 
To make Appendix D [specifically D-2.3.14.] applicable with respect to wired glass assemblies.